1. Overview and Capability Boundary
CJ/T 188 is a common protocol for domestic water/heat/gas meters, common versions are CJ/T 188-2004 and CJ/T 188-2018. Links are commonly two types: RS-485 (Serial) and Serial Server to TCP.
NG Gateway's CJ/T188 southward driver (ng-driver-cjt188) is a polling collection driver centered on DI Schema Driven Parsing.
Important (Capability Boundary)
- Read-Only: Driver does not support
execute_actionandwrite_point(Downlink not implemented), please do not configure any Action/Write Point capability for this driver. - Active Collection Only: Driver is used for
collection_type = Collectionscenario (Gateway schedulescollect_datato initiate reading).
2. Configuration Model
2.1 Channel Driver Configuration
2.1.1 version (Protocol Version)
V2004V2018
2.1.2 connection.type (Connection Type)
Serial: Serial/RS-485 (Recommended for direct connection to 485 bus)Tcp: TCP (Serial server/Gateway)
Serial Parameters (When connection.type = Serial):
connection.port: Serial port pathconnection.baud_rate: Baud rateconnection.data_bits: Data bits (Default 8)connection.stop_bits: Stop bits (Default 1)connection.parity: Parity
TCP Parameters (When connection.type = Tcp):
connection.host: Hostconnection.port: Port
2.1.3 max_timeouts (Consecutive Timeout Trigger Reconnection)
This field directly drives "Timeout Trigger Reconnection" logic:
max_timeouts = 0: Disable "Consecutive Timeout Trigger Reconnection" (But IO/Transport errors still trigger reconnection)max_timeouts > 0: WhenConsecutive Request Timeout Count>max_timeouts, driver requests supervisor to disconnect and rebuild session
Suggestion
- Not recommended to set
max_timeoutsto 1 (Prone to jitter reconnection), default 3 is usually more stable. - If field link jitter is high and device response is slow: Prioritize increasing
connection_policy.read_timeout_ms, then increasemax_timeouts.
2.1.4 wakeup_preamble (Preamble Wakeup Code)
wakeup_preamble is a u8 array (Default [0xFE, 0xFE, 0xFE, 0xFE]). The driver will write this byte sequence to the link before sending each CJ/T 188 frame:
- Suitable for some RS-485 meters that "Need 0xFE to wake up"
- If explicitly not needed, can be configured as empty array
[]to reduce bandwidth and write overhead
2.2 Device Driver Configuration
Key fields of Device driver_config:
meterType: Meter Type (T, 1 byte integer 0..=255)- Decides MeterTypeFamily: Water/Heat/Gas/Custom
- MeterTypeFamily decides schema selection: Same DI may have different field structures in different families
address: 14-digit hex string, representing A6..A0 (High byte first)- Driver automatically converts to protocol wire order A0..A6 (
Low byte first)
- Driver automatically converts to protocol wire order A0..A6 (
2.3 Point Driver Configuration
di: 4-digit hex (2-byte DI, e.g.,901F)field_key: Field key in that DI schema (e.g.,current_flow,datetime)
Modeling Best Practice
One DI usually contains multiple fields (e.g., 901F contains current_flow/datetime/status simultaneously):
- Multi-field Collection: Create multiple Points, same DI, different field_key
- Performance: Driver reads grouped by DI, only initiates one request for same device same DI, then distributes results to multiple Points (Reduce request count, higher throughput)
3. Data Type Mapping Table
3.1 Schema DataFormat → "Source Scalar" Semantics
Codec layer first decodes bytes into a "Source Scalar" (decoded scalar), then produces final NGValue according to Point's data_type + scale.
| Schema DataFormat | Byte Semantics | Source Scalar Type | Remark |
|---|---|---|---|
BCD { decimals } | BCD Numeric (With decimals) | f64 | Decimals fixed by schema, Point does not configure decimals |
BCDInteger | BCD Integer | u64 | Suitable for count/work hours/date(day) etc. |
Binary | Little Endian Unsigned Integer | u64 | Used for bitset/enum/count etc. |
DateTime | 7-byte BCD Time | i64 | Output as epoch ms (UTC) |
Status | 2-byte Status Bits (Little Endian) | u64 | Semantics is u16, easy for bitwise parsing |
BCDWithUnit { data_length, decimals } | BCD Numeric + 1-byte Unit Code | f64 | Unit code currently not reported with value |
3.2 data_type Coercion Matrix
Driver follows unified rules for coercion of each field: First get Source Scalar (f64/u64/i64), Apply scale (If any), then produce final NGValue by data_type.
Target data_type | Supported Source Scalar | Produced NGValue | Key Semantics |
|---|---|---|---|
Boolean | f64/u64/i64 | Boolean | != 0 treated as true |
Int8/Int16/Int32/Int64 | f64/u64/i64 | Corresponding Integer | With scale will do round() and range check; Without scale u64/i64 takes integer fast path (More precise) |
UInt8/UInt16/UInt32/UInt64 | f64/u64/i64 | Corresponding Unsigned Integer | Same as above; i64 to UInt* requires non-negative and representable |
Float32/Float64 | f64/u64/i64 | Corresponding Float | With scale directly scales |
String | f64/u64/i64 | String | Numeric to String |
Binary | f64/u64/i64 | Binary | Numeric written to bytes in Big Endian (Only recommend for debug/passthrough, not as business value) |
Timestamp | f64/u64/i64 | Timestamp | Represents epoch ms; Source scalar (i64) produced by DateTime decoding recommended to configure Timestamp directly |
Note
Status field semantics is u16 bitset. Recommend data_type=UInt16, then split bitwise in Rule Engine/Northward side (e.g., Valve Switch, Battery Undervoltage, etc.).
4. Supported DI / field_key
Driver built-in schema quantity is large (Contains massive range DIs), recommend understanding by "Meter Family + DI Range". Full list and explanation see ./address-di.md, here gives overview:
- Water/Gas
901FD120..D12B(12 items)D200..D2FF(256 items)D300..D3FF(256 items, Timed Freeze)D400..D4FF(256 items, Instant Freeze)
- Heat
901F911FD120..D12BD200..D2FF
- Common (Universal for all meter families)
907F,8102,8103,8104,8105
5. Typical Modeling Examples
5.1 Water/Gas 901F: Collect Cumulative, Time, Status Simultaneously
Recommend creating 3 Points (Same Device Same DI, Read only once):
di=901F+field_key=current_flow+data_type=Float64(Recommendunit=m³)di=901F+field_key=datetime+data_type=Timestampdi=901F+field_key=status+data_type=UInt16
5.2 Freeze Data D3XX/D4XX: Time + Cumulative + Instantaneous
Water/Gas freeze DI will produce freeze_datetime (Recommend Timestamp), cumulative_flow, flow_rate, temperature, pressure etc.; Recommend using Float64 for numeric fields.
6. Troubleshooting
- No Data Read / Frequent Timeout:
- Prioritize increasing
connection_policy.read_timeout_ms - Confirm serial parameters consistent with field; retain default
wakeup_preambleif necessary - Reasonably set
max_timeouts(Too small causes jitter reconnection)
- Prioritize increasing
- Log "No schema found":
- Confirm
meterTypeis correct (Meter Family decides schema selection) - Confirm DI is within current implementation support range (See
address-di.md)
- Confirm
- Log "Point value not produced":
field_keymight be misspelled, or does not belong to that DI/Meter Family