1. Protocol Introduction
DL/T 645 is a common protocol for domestic energy meters/multi-function meters, typical versions are DL/T 645-1997 and DL/T 645-2007 (Most common in the field). The protocol often runs on RS-485, and also often converted to TCP via serial server.
The goal of NG Gateway DLT645 driver is: Stably poll multiple meters on one bus, and decode readings corresponding to DI into unified NGValue.
2. Configuration Model
2.1 Channel Configuration
One RS-485 bus (or one TCP serial server connection) is modeled as a Channel.
2.1.1 version (Protocol Version)
DL/T 645-1997DL/T 645-2007
Version affects
- DI length (1997: 2 bytes; 2007: 4 bytes)
- Control code and some semantics
2.1.2 connection.kind (Connection Type)
Serial: Serial/RS-485 (Recommended for direct connection to 485 bus)Tcp: TCP (Serial server/Gateway)
Serial Parameters (When connection.kind = Serial):
connection.port: Serial port pathconnection.baud_rate: Baud rateconnection.data_bits: Data bits (Default 8)connection.stop_bits: Stop bits (Default 1)connection.parity: Parity
TCP Parameters (When connection.kind = Tcp):
connection.host: Hostconnection.port: Port
2.1.3 Advanced Parameters
maxTimeouts: Trigger reconnection after consecutive timeouts exceed this value (Default 3)wakeupPreamble: Send preamble wakeup code (Default[0xFE,0xFE,0xFE,0xFE])
Best Practice
- In RS-485 scenarios, preamble wakeup code is a common compatibility strategy; if field device explicitly does not need it, can be configured as empty array to reduce bandwidth.
- Timeout and Reconnection: Try not to set
maxTimeoutsto 1 (Prone to jitter reconnection), default 3 is usually more stable.
2.2 Device Configuration
Each Device corresponds to a meter:
address: Meter address (12-digit number, example123456789012)password: Password (Default00000000, generally hex string)operatorCode: Operator code (Optional)
TIP
For detailed explanation of Address/DI, see DL/T Address Syntax.
2.3 Point Configuration
di: Data Identifier (2007 usually 8-digit hex; 1997 uses low 16-bit)decimals: Decimal places (Optional, used for BCD decoding)
Point's data_type affects forced type conversion and scale after BCD decoding.
2.4 Action Configuration
Action is used to encapsulate a set of "Write Meter/Control/Maintenance Command" operations; Action itself does not carry protocol detail configuration.
- Key Semantics: DL/T 645 control code/DI/decimal places and other protocol details should be configured on Action's
inputs(Parameter), i.e., each parameter specifies the function and encoding details viaParameter.driver_config.
Parameter-level driver configuration fields (Each input parameter):
functionCode: Required. Function Code as follows:Enum Name Description BroadcastTimeSyncBroadcast Time Sync ReadDataRead Data ReadNextDataRead Next Data ReadAddressRead Communication Address WriteDataWrite Data WriteAddressWrite Communication Address FreezeFreeze Command UpdateBaudRateUpdate Baud Rate ModifyPasswordModify Password ClearMaxDemandClear Max Demand ClearMeterClear Meter ClearEventsClear Events di: Optional. Some actions need to specify DI (e.g., "Write a data item"); actions not needing DI can omit.decimals: Optional. Decimal places for numeric BCD encoding/decoding (Default strategy see table below).
3. Data Type Mapping Table
3.1 Point (Uplink) Recommended Mapping
Most DL/T 645 readings are BCD (0x33 offset removed):
- Driver will first BCD → f64, then force convert according to Point's
data_type, and applyscale(if configured). decimalscontrols BCD decoding decimal places (Default strategy: Numeric defaults to 0 or 2, see table below).
| DataType | Recommended Scenario | Decoding Rule (Implementation Semantics) | Remark |
|---|---|---|---|
| Float32 / Float64 | Most "Readings/Energy/Power/Voltage" etc. | BCD → f64 → Float (Apply scale) | Most Recommended, least prone to pitfalls |
| Int8/16/32/64 | Field explicitly signed integer reading | BCD → f64 → Integer (Apply scale) | Watch for overflow and decimal places |
| UInt8/16/32/64 | Count/Sequence/Unsigned reading | BCD → f64 → Unsigned Integer (Apply scale) | Watch for overflow |
| Boolean | Status bit/Switch (Implemented as bit0) | payload[0] & 0x01 != 0 | Only suitable for data items with clear 0/1 semantics |
| String | Meter returns printable text | Try UTF-8/ASCII; trim trailing 0; fallback Binary on failure | |
| Binary | Raw bytes | Raw bytes | Use when unsure of encoding or upper layer parsing needed |
| Timestamp | Use with caution | Current implementation treats BCD value as timestamp numeric value and force converts (i64 ms) | If device returns "YYMMDDhhmmss" format, do not use Timestamp; please use String/Binary and convert on edge side |
3.2 Action Parameter (Downlink) DataType Selection (Write Encoding)
DL/T 645 action write uses Dl645Codec::encode_parameter_value, with explicit whitelist for DataType:
| Parameter.data_type | Supported | Default decimals | Encoding Rule |
|---|---|---|---|
| Float32 / Float64 | ✅ | 2 | Numeric → BCD (Signed) |
| Int8/16/32/64 | ✅ | 0 | Numeric → BCD (Signed) |
| UInt8/16/32/64 | ✅ | 0 | Numeric → BCD (Unsigned) |
| Boolean | ✅ | - | 0x00 / 0x01 |
| String | ✅ | - | Raw bytes (UTF-8/ASCII) |
| Binary / Timestamp | ❌ | - | Driver returns config error |
Best Practice
- Write value range must be clear: DL/T 645 Action write does not automatically apply
scale(scale is Point metadata); you need to write the value expected by the device directly (and control BCD decimal places withdecimals). - Use Float if possible: Prefer Float32/Float64 for reading points, reducing problems caused by "Integer Overflow/Truncation/Decimal Places".