1. Protocol Introduction
DNP3 (Distributed Network Protocol) is commonly used in SCADA scenarios such as power and water utilities. It supports Integrity Scan and Event Scan, and can run over TCP/UDP/Serial.
NG Gateway DNP3 driver acts as Master communicating with Outstation:
- Periodically execute Integrity Scan (Class 0/1/2/3)
- Periodically execute Event Scan (Class 1/2/3)
- Support some downlink commands (CROB/Analog Output/Restart, etc.)
2. Configuration Model
2.1 Channel Configuration
2.1.1 connection.type (Connection Type)
serial: Serial/RS-485 (Recommended for direct connection to 485 bus)tcp: TCP (Serial server/Gateway)udp: UDP (Serial server/Gateway)
Serial Parameters (When connection.type = serial):
connection.port: Serial port pathconnection.baud_rate: Baud rateconnection.data_bits: Data bits (Default 8)connection.stop_bits: Stop bits (Default 1)connection.parity: Parity
TCP Parameters (When connection.type = tcp):
connection.host: Hostconnection.port: Port
UDP Parameters (When connection.type = udp):
connection.host: Hostconnection.port: Portconnection.localPort: Optional, local UDP port
2.1.2 Link Layer Address
localAddr: Master address (0..65519)remoteAddr: Outstation address (0..65519)
2.1.3 Scan and Timeout
responseTimeoutMs: Response timeout (Default 5000)integrityScanIntervalMs: Integrity scan interval (Default 20000)eventScanIntervalMs: Event scan interval (Default 1000)
2.2 Device Configuration
Driver layer device configuration is empty (device used for logical grouping).
2.3 Point Configuration
Points are located by "Object Group + Index":
group: Object Group (BinaryInput/AnalogInput/Counter/OctetString etc.)index: Index (Starting from 0)
2.4 Action Configuration
Action is used to encapsulate a set of "Downlink Command" operations; Action itself does not carry protocol detail configuration.
- Key Semantics: DNP3 command type and target index should be configured on Action's
inputs(Parameter), i.e., each parameter specifies the command and object index to issue viaParameter.driver_config.group/index. - Parameterless Action: Commands like
WarmRestart/ColdRestartusually do not need value; you can create an Action with empty inputs, and useAction.commandto represent the action semantics (driver will ignore value).
Parameter-level driver configuration fields (Each input parameter):
group: Command Type (CROB/AnalogOutputCommand/WarmRestart/ColdRestart)index: Target Index (Required forCROB/AnalogOutputCommand; Ignored for Restart class)
TIP
For details on group/index, see Object Group/Index/Command Type
3. Data Type Mapping Table
3.1 Point (Uplink) Recommended Mapping
| Point group | Raw Value Type | Recommended DataType | Description |
|---|---|---|---|
| BinaryInput / BinaryOutputStatus (bool class) | bool | Boolean | Most recommended |
| AnalogInput (Analog) | f64 | Float32 / Float64 | Optional Int*/UInt* if integer needed, but watch for overflow and precision |
| Counter / FrozenCounter (Cumulative) | u64 | UInt64 (Or Int64) | Cumulative usually unsigned; select Int64 only if negative value agreed by field |
| OctetString | bytes | Binary / String | String will try UTF-8, fallback to Binary on failure |
Note
DNP3 has many object groups, for full list and modeling suggestions see Object Group/Index/Command Type. The table above gives the most common and stable combinations.
3.2 WritePoint (Downlink Write Point) DataType Selection
WritePoint only supports writing the following groups:
BinaryOutput→ UsesCROB(Control Relay Output Block)AnalogOutput→ UsesAnalogOutputCommand(Group 41)
And the driver performs Strict Type Validation on value (Type mismatch directly rejected), so point.data_type must be selected correctly.
| Write Target (point.group) | Underlying Command | Recommended DataType | Value Description |
|---|---|---|---|
| BinaryOutput | CROB | UInt8 (Recommended) | Only supports UInt8 Control Code: Value must be selected from gateway allowed value table (See crob.md) |
| AnalogOutput | AnalogOutputCommand | Int16 / Int32 / Float32 / Float64 | DataType decides Group41 Variation (Var2/Var1/Var3/Var4) |
DataType to Group41 Variation Mapping (Key)
Core Mechanism: DataType directly determines the Variation used by DNP3 write command:
| DataType | DNP3 Variation | Protocol Meaning | Value Range |
|---|---|---|---|
| Int16 / UInt16 | Group41Var2 | 16-bit Analog Output | -32768 ~ 32767 |
| Int32 / UInt32 | Group41Var1 | 32-bit Analog Output | -2^31 ~ 2^31-1 |
| Float32 | Group41Var3 | Single-precision Float | IEEE 754 float |
| Float64 | Group41Var4 | Double-precision Float | IEEE 754 double |
Why no need to configure Variation?
NG Gateway adopts Simplified Modeling strategy, this design simplifies configuration, users do not need to understand protocol details, while ensuring protocol compatibility. See DataType and Variation Mapping.
3.3 Action Parameter (Downlink Action Parameter) DataType Selection
Action Parameter follows same rules as WritePoint: Each parameter carries group/index, and parses value by its data_type.
group=CROB: Recommenddata_type=UInt8, value as CROB Control Code(u8) (Select from gateway allowed value table)
Note
Value type is u8, but driver only accepts 48 explicit combinations (Others will be rejected), see crob.md.
group=AnalogOutputCommand: value only supportsInt16/Int32/Float32/Float64(Otherwise driver returns error)
3.3.1 How to configure "Protocol Level Fields" of CROB Parameter?
To ensure WritePoint is Simple and Safe, WritePoint path DOES NOT Provide control capability for CROB's count/on/off etc. "Protocol Level Fields":
- WritePoint (BinaryOutput): Only supports issuing
value=ControlCode(u8), cannot controlcrobCount/crobOnTimeMs/crobOffTimeMs - Action (CROB): Control
crobCount/crobOnTimeMs/crobOffTimeMsvia Parameter Level modeling fields (Thus different inputs within the same Action can configure different pulse timing and counts)