1. Protocol Introduction and Common Scenarios

EtherNet/IP (Industrial Protocol) is an industrial automation network protocol developed and maintained by ODVA (Open DeviceNet Vendor Association), helping to achieve automated control and data exchange between devices, such as manufacturing, energy, transportation logistics, construction, etc.

NG Gateway Ethernet/IP driver connects to PLC as a client and reads/writes by Tag name.

2. Configuration Model

2.1 Channel Configuration

  • host: PLC Address (IPv4/hostname)
  • port: Default 44818
  • timeout: Request timeout (ms, default 2000)
  • slot: Slot number (Default 0)

TIP

Slot semantics depend on PLC model/rack structure; if unsure, keep default and verify read/write with a known Tag.

2.2 Device Configuration

Driver layer device configuration is empty (device used for logical grouping).

Grouped collection

When multiple business Devices exist under the same Channel, Ethernet/IP driver will enable grouped collection: Collector will merge points of these Devices into one collect_data(items) call, driver will merge Tags to execute batch read (chunked batch read), then split into respective NorthwardData outputs by device_id.

2.3 Point Configuration

  • tagName: Tag Name (Required), e.g.:
    • MyTag
    • Program:Main.MyTag

2.4 Action Configuration

Action is used to encapsulate a set of "Write Tag" operations; Action itself does not carry protocol detail configuration.

  • Key Semantics: Ethernet/IP write target Tag must be configured on Action's inputs(Parameter), i.e., each parameter specifies the Tag to write via Parameter.driver_config.tagName.
  • Why Design This Way: An Action often needs to write multiple Tags (e.g., issue multiple set points at once), Action is just an abstraction of "Operation Set"; truly configurable protocol fields must fall on Parameter itself.

Parameter-level driver configuration fields (Each input parameter):

  • tagName: Tag Name (Required), e.g., Program:Main.MyTag

3. Value Type Conversion

  • Read (uplink): PlcValue returned by PLC will first be decoded by Point's wire data type, then apply Point's logical data type + Transform (transformDataType/transformScale/transformOffset/transformNegate) to output NGValue.
  • Write (downlink): Value issued by northward is treated as logical value, core will first execute logical→wire (including Transform inverse), driver then encodes as PlcValue to write to PLC according to wire data type.

Recommended Reading

For full link of Transform, non-numeric limits, value range consistency of min/max, see: Data Types and Transform Configuration.

Explanation

Gateway side will try its best to convert according to data_type, but PLC side will still check Tag's real CIP type. Therefore, when data_type is chosen wrongly, writing may still fail (Type mismatch/Out of bounds/Truncation, etc.).

This table gives "Least Pitfall" modeling choices: Keep data_type consistent with PLC Tag's real type (Most stable for both read and write).

PLC Tag Type (CIP)Recommended DataTypeDescription
BOOLBoolean-
SINTInt8-
INTInt16-
DINTInt32-
LINTInt64-
USINTUInt8-
UINTUInt16-
UDINTUInt32-
ULINTUInt64-
REALFloat32-
LREALFloat64-
STRINGString-
LINT (Unix epoch ms)TimestampSemantic Convention: i64 millisecond timestamp; encoded as LINT on write

TIP

For complex types (Array/UDT/Structure) support status and alternative modeling strategies, see Tag Modeling.

Core Semantics

  • Coercion by data_type (With Range Check): e.g., PLC returns UDINT=42, point declares Int32, will report NGValue::Int32(42); if out of range (e.g., UDINT > i32::MAX), will report error and skip point.
  • Scale/Offset/Negate by Transform (Read/Write Consistent): If you need engineering value semantics (e.g., scaled integer, zero offset), please use Point's Transform (Both uplink wire→logical and downlink logical→wire will take effect).
  • Special Rules when PLC returns STRING:
    • data_type=String: Report string as is.
    • data_type=Boolean: Parse by SDK rules (true/false/1/0/on/off/yes/no/y/n/t/f, ignore case and trim whitespace).
    • data_type=Timestamp: Prioritize parsing RFC3339; otherwise parse string as "Numeric Timestamp" to epoch ms (With range check).
    • Other Numeric Types: First parse f64, then output by logical data type + Transform.

Core Semantics

  • Cast + Range Check by data_type: e.g., parameter declares Int32, input is "123" (String), will try to parse and write DINT(123).
  • Write will apply Transform's Inverse: Northward writes logical value, written to PLC is wire value (Inversed).
  • Conversion Failure returns ValidationError: e.g., Out of bounds, NaN/Inf, Cannot parse string, etc.
  • Compatible Input for Boolean (When writing data_type=Boolean):
    • true/false
    • Numeric (0=false, Non-0=true)
    • String (Same as uplink token rules)

3.4 DataType Selection Suggestion

  • First Priority: Align with PLC Tag Real Type: This is the only solution for "Stable Read/Write". Gateway's cast/coercion is fault tolerance capability, not for arbitrary type mixing.
  • Point (Read) can do coercion, but bear consequences:
    • e.g., PLC UDINT + data_type=Int32: Can report as long as value is within range; out of range will error and skip point.
    • e.g., PLC REAL + data_type=Int32: Will truncate float to integer first, may lose decimals.
  • Action Parameter (Write) must be more cautious:
    • Even if gateway can cast "123" to DINT(123), if PLC Tag is REAL or STRING, PLC may still reject write due to CIP type mismatch.
    • Conclusion: Write data_type should strictly align with PLC Tag type.
  • Binary Support Status (Important):
    • Binary currently not supported by driver (Field most common is SINT[]/BYTE[] array, while current underlying PlcValue only supports scalar and UDT, not array/byte string).
    • Alternative modeling strategy see Tag Modeling.
  • Timestamp Best Practice:
    • Timestamp semantics fixed as i64 milliseconds (epoch ms).
    • Encoded as PLC LINT on write.
    • Not recommended to use ULINT to carry timestamp: Exceeding i64::MAX will be judged as illegal timestamp and conversion fails.

Best Practice

  • If your PLC has UDT/Structure/Array: Suggest providing "Scalar Mirror Tag" on PLC side (Split members into independent Tags), or providing mapping node on PLC/OPC Server side; current version driver will error on complex types.
  • Verify read/write path and slot semantics with a "Simple Scalar Tag" (e.g., DINT counter) first, then model in bulk.

3.5 Common Failure Modes and Troubleshooting

  • Unsupported PlcValue type ...
    • Meaning: PLC returned complex type (e.g., UDT/Structure/Array), current driver cannot map to NGValue.
    • Handling: Provide scalar mirror Tag on PLC/Server side as suggested in Tag Modeling, then model on gateway side.
  • typed conversion failed ...
    • Meaning: Read path wire→logical conversion failed (Common causes: Out of bounds, String cannot parse to Number/Bool, Timestamp out of bounds, Transform constraint not met).
    • Handling: Check if wire/logical types align; Check Transform config (Especially scale=0, non-numeric mapping, huge integer + non-identity Transform).
  • write value cast failed ... / ValidationError
    • Meaning: Cast failed before write (Out of bounds, NaN/Inf, String cannot parse, etc.).
    • Handling: Check Parameter/Point data_type and input value; Input numeric type instead of string if necessary.
  • PLC side write failed (CIP type mismatch etc.)
    • Meaning: Gateway side conversion successful, but PLC rejected (Tag type mismatch, Permission/Run mode restriction, Out of bounds, etc.).
    • Handling: Prioritize letting write data_type strictly equal PLC Tag type; Check Tag type and write permission/status in PLC tool side.