1. Protocol Introduction and Common Scenarios

Mitsubishi PLC's MC protocol (MELSEC Communication Protocol) is commonly used to read/write registers/coils (devices) of Mitsubishi PLCs (A/QnA/Q/L/iQ-R etc.). Different series have differences in frame format and batch capabilities.

NG Gateway MC driver connects to PLC as a client, performs batch read/write via MC addresses (e.g., D100, X1A0, D20.2), and maps results to unified NGValue.

2. Configuration Model: Channel / Device / Point / Action

2.1 Channel Configuration

MC Channel configuration (Editable fields) is defined by @ng-gateway-southward/mc/src/metadata.rs, corresponding to runtime structure McChannelConfig:

  • host: PLC IP/hostname
  • port: Port (Default 5001, depends on field PLC/Gateway configuration)
  • series: PLC Series (A / QnA / Q/L / iQ-R)
  • maxPointsPerBatch: Max points per batch (Used for batch read/write planning)
  • maxBytesPerFrame: Max bytes per frame (Used to prevent frame from being too large)
  • concurrentRequests: Concurrent request count (Default 1, suggest increasing cautiously)

Why series is needed:

  • Different series correspond to different frame variants and batch limits (Driver will choose frame variant and limits accordingly).

2.2 Device Configuration

Driver layer device configuration is empty (device used for logical grouping).

Grouped collection

When multiple business Devices exist under the same Channel, MC driver will enable grouped collection: Collector will merge points of these Devices into one collect_data(items) call, driver will merge points and execute batch read, then split into respective NorthwardData outputs by device_id.

2.3 Point Configuration

Point driver configuration fields:

  • address: MC Address (Required)
  • stringLenBytes: String Length (Bytes, Optional, only used when data_type=String requires fixed length)

Address syntax details see ./addressing.md.

2.4 Action Configuration

Action is used to encapsulate a set of "Write Address" operations; Action itself does not carry protocol detail configuration.

  • Key Semantics: MC write target address should be configured on Action's inputs(Parameter), i.e., each parameter specifies the MC address to write via Parameter.driver_config.address.
  • Usage Suggestion:
    • Single address write: Create an Action, put one parameter (one address) in inputs.
    • Multi-address batch write: Define multiple parameters (multiple addresses) under the same Action, one RPC issue can complete multi-point writing.

Parameter-level driver configuration fields (Each input parameter):

  • address: MC Address (Required)
  • stringLenBytes: String Length (Bytes, Optional, only used when data_type=String requires fixed length)

3. Data Type Mapping Table (MC ↔ DataType)

Value encoding/decoding logic is located at @ng-gateway-southward/mc/src/codec.rs (McCodec), batch planning and "Word Length" rules in mc/src/driver.rs::words_for_data_type.

MC "Word" is 16-bit. Driver will calculate number of words to read/write based on data_type (String needs extra length).

DataTypeWord CountEncodingDescription
Boolean11 byte (0/1)Bit devices (X/Y/M etc.) recommend using only Boolean
Int8 / UInt81little-endian (Low byte valid)Treated as 1 word
Int16 / UInt161little-endian
Int32 / UInt32 / Float322little-endianFloat32 is IEEE754
Int64 / UInt64 / Float644little-endianFloat64 is IEEE754
Stringceil(stringLenBytes/2)bytesMust configure stringLenBytes (Same for Point and Action Parameter)
Binary--Not supported in current version (Point/Action will report config error)
Timestamp--Not supported in current version (Point/Action will report config error)

3.2 Read Path (MC bytes → NGValue)

  • Numeric types use little-endian decoding (Compliant with MC binary spec).
  • String: Read fixed length bytes; driver does not auto trim, suggest agreeing on "0 termination/padding rules" on upper layer.

3.3 Write Path (NGValue → MC bytes)

Writing also uses little-endian encoding; suggest data_type consistent with target device real storage type, otherwise "Write in read back fails/Value incorrect" may occur.

Best Practice

  • String strongly recommends clarifying stringLenBytes consistent with PLC side storage length, and agreeing on padding/truncation rules.
  • Bit devices (X/Y/M etc.) suggest using only Boolean, avoiding unpredictable semantics of "Writing bit as word".

4. Advanced Documentation

  • MC Address Syntax and Dec/Hex Rules: See ./addressing.md
  • Batch Read/Write/Frame Size/Concurrency Tuning: See ./batching.md