1. Protocol Introduction

Modbus is a classic industrial field communication protocol, with common forms including Modbus TCP (Ethernet) and Modbus RTU (Serial/RS-485). It uses "Register/Coil" as core abstractions:

  • Coils: bit (Usually Read/Write)
  • Discrete Inputs: bit (Usually Read-Only)
  • Holding Registers: 16-bit register (Usually Read/Write)
  • Input Registers: 16-bit register (Usually Read-Only)

NG Gateway Modbus driver adopts a Fully Asynchronous, Zero-Copy architecture, performing batch read/write of points with high throughput and low overhead on the gateway side. Supports Smart Cast (Intelligent Type Conversion) and Automatic Batch Planning.

2. Configuration Model

2.1 Channel Configuration

Channel is the boundary of "Connection and Session": The same TCP connection or the same RS-485 serial line should be modeled as a Channel.

2.1.1 connection.kind (Connection Type)

  • tcp: Modbus TCP
  • rtu: Modbus RTU (Serial)

2.1.2 TCP Parameters (When connection.kind = tcp)

  • connection.host: Remote host (IPv4 or hostname, excluding schema/port)
  • connection.port: Port, default 502

Suggestion

  • Field devices mostly have fixed IPs, it is recommended to fill in IP directly; avoid extra uncertainty introduced by DNS resolution.

2.1.3 RTU Parameters (When connection.kind = rtu)

  • connection.port: Serial port path
    • Linux Example: /dev/ttyUSB0
    • Windows Example: COM3
  • connection.baudRate: Baud rate (Default 9600)
  • connection.dataBits: Data bits (5/6/7/8, Default 8)
  • connection.stopBits: Stop bits (1/2, Default 1)
  • connection.parity: Parity (None/Odd/Even, Default None)

2.1.4 byteOrder / wordOrder

Modbus register is a 16-bit word; when point data type is 32/64-bit, it spans multiple registers. Different devices have differences in "Byte/Word Order" implementation:

  • byteOrder: Order of two bytes inside a register (BigEndian/LittleEndian)
  • wordOrder: Order of words when multiple registers are used (BigEndian/LittleEndian)

Typical Combinations:

  • Common PLC: byteOrder=BigEndian, wordOrder=BigEndian
  • Some devices (Especially legacy devices) use "Word Swap" for 32-bit/64-bit: wordOrder=LittleEndian

Suggest confirming in host computer/manufacturer manual; if the read float value is "obviously absurd", prioritize checking byte/word order.

2.1.5 tcpPoolSize

tcpPoolSize is used to improve Modbus TCP throughput: The driver maintains a TCP connection pool, and selects connections in a round-robin manner within the pool during collection, thereby allowing multiple requests in flight (Still subject to core concurrency and driver internal planning constraints).

  • Default Value: 1
  • Recommended Range: 1..=32 (Too large usually yields insignificant benefits and increases PLC/Gateway resource consumption)

WARNING

Only effective for connection.kind=tcp; RTU will force single flight (Effective value=1). When you configure tcpPoolSize > 32, the driver will clamp to 32 at runtime.

2.1.6 Batch Read Planning Parameters

FieldScopeDefaultDescription
maxBatchRegisters0x03/0x04 (Register Read)120Max span (number of words) for a single read request. Protocol hard limit <=125, driver will clamp
maxGapRegisters0x03/0x04 (Register Read)1Max "Gap" (word address difference) allowed when merging adjacent points
maxBatchBits0x01/0x02 (Bit Read)2000Max span (number of bits) for a single read request. Protocol hard limit <=2000
maxGapBits0x01/0x02 (Bit Read)500Max "Gap" (bit address difference) allowed when merging adjacent points

WARNING

maxBatch* represents "Total quantity of a range read" (span), not "Number of points".

2.2 Device Configuration

Device represents a Slave.

  • slaveId: Slave ID (0-255)

2.2.1 Group collection

Modbus driver enables group collection in Polling collection path, grouping key is slaveId:

  • Same slaveId: Collector will merge multiple business Devices into one collect_data(items) call, driver will merge points and execute batch read (read request count closer to theoretical minimum), then split into respective NorthwardData outputs by business device_id.
  • Different slaveId: Will be split into different groups for separate collection.

2.3 Point Configuration

  • functionCode:
    • ReadCoils(0x01) / ReadDiscreteInputs(0x02)
    • ReadHoldingRegisters(0x03) / ReadInputRegisters(0x04)
  • address: Start address (0..65535, 0-based)
  • quantity: Read quantity (Coil bit count or Register word count)

2.3.1 wire/logical data type & Transform (Must Read)

Modbus dataType is wire data type (Protocol/Memory layout semantics): It determines how the driver decodes from register/coil and how to write back.

If you want northward to see "Engineering Value" (e.g., register contains scaled integer), please use Point's Transform (logical semantics):

  • transformDataType: logical data type (logical=wire if empty)
  • transformScale/transformOffset/transformNegate: Numeric affine transformation

Recommended Reading

For full explanation, uplink/downlink links, min/max value range, and large integer/non-numeric limits, see: Data Types and Transform Configuration.

0-based vs 1-based address problem (Must Read)

The address in the driver here is Protocol Layer 0-based Address (UI validates min 0). But many manufacturer manuals use 1-based or "Logical Address" like 4xxxx/3xxxx.

You need to convert manual address to 0-based:

  • If manual says 40001 corresponds to 1st Holding Register, then protocol address is usually 0 (40001-40001).
  • If manual directly gives "Register Offset 0/1", follow manual definition.

It is recommended to use a "Known Fixed Value" point for validation (e.g., Device Model/Firmware Version register), calibrate the address system first, then model in bulk.

How to calculate quantity

The meaning of quantity depends on functionCode:

  • Coils/DiscreteInputs: Unit is bit (Coil count)
  • Holding/InputRegisters: Unit is word (16-bit)

For register reads, it is recommended to calculate quantity by data_type (See 3. Data Type Mapping Table). If quantity is too small, the driver will try to perform Smart Cast (e.g., read 1 word convert to Float32); if too large, it will truncate or pad.

2.4 Action Configuration

Action is used to encapsulate a set of "Write Coil/Write Register" operations.

  • functionCode:
    • WriteSingleCoil(0x05) / WriteMultipleCoils(0x0F)
    • WriteSingleRegister(0x06) / WriteMultipleRegisters(0x10)
  • address: Start address
  • quantity: Write quantity

Automatic Function Code Inference

For northward write_point (Single Point Write) operation, if the point defines a read function code (e.g., ReadHoldingRegisters), the driver will automatically infer the write function code based on quantity:

  • quantity <= 1 -> WriteSingleRegister (0x06)
  • quantity > 1 -> WriteMultipleRegisters (0x10)

3. Data Type Mapping Table (Smart Codec)

The driver has a built-in powerful codec supporting flexible conversion from register stream to strongly typed values.

3.1 Register Types (0x03/0x04)

DataTypeRecommended quantity (words)Decoding BehaviorSmart Cast (Degrade Compatibility)
Boolean1First word != 0 is true-
Int161Standard 16-bit signed integerRead 4 words (i64) truncate to i16
UInt161Standard 16-bit unsigned integerRead 4 words (u64) truncate to u16
Int322Standard 32-bit signed integerIf quantity=1, read i16 and promote to i32
UInt322Standard 32-bit unsigned integerIf quantity=1, read u16 and promote to u32
Float322IEEE754 Single Precision FloatIf quantity=1, read i16 and convert to f32
Float644IEEE754 Double Precision FloatIf quantity=2, read f32 and convert to f64
Int644Standard 64-bit signed integerIf quantity=2, read i32 and promote to i64
UInt644Standard 64-bit unsigned integerIf quantity=2, read u32 and promote to u64
Timestamp2 or 44 words (8 bytes): Parse as i64 millisecond timestamp
2 words (4 bytes): Parse as u32 second timestamp and auto multiply by 1000
-
StringNUTF-8 String, auto remove trailing \0-
BinaryNRaw byte stream-

"Fixed Length Block + Padding" Convention for String Points (Must Read)

Modbus protocol itself does not have a "String Register" type. String reading relies entirely on Device side data storage convention. Current driver behavior for String is:

  • Restore quantity registers into byte stream according to byteOrder/wordOrder;
  • Then only remove trailing consecutive 0x00 (Remove tail \0 padding), then decode as UTF-8 (Invalid bytes will be shown as replacement characters).

Therefore you need to pay special attention:

  • quantity must be sufficient: Unit is register (word, 2 bytes). E.g., "String length 10 bytes" usually needs quantity = 5.
  • Device write suggests "Full Overwrite + 0x00 Padding": Fill the entire fixed-length register block; pad remaining part with 0x00.
    • Ex: Fixed length 10 registers (20 bytes) storing "a", suggest writing 0x61 0x00 then pad remaining 18 bytes with 0x00.
  • Do not just write a\0 and leave remaining registers uncleared: If tail has old data and not 0x00, driver will not truncate at first 0x00, may appear as "a\0xxxx..." (Containing invisible characters/dirty tail), looking like "String incorrect".

If field device cannot guarantee clearing tail, suggest unifying "Fixed Length Block 0 Padding" protocol on device side (or host computer write side); and first verify byteOrder/wordOrder correctness with a known string register.

Details

Smart Cast Example Scenario: Device has a temperature value, actually Int16 (255 = 25.5°C), but you defined it as Float32 in platform.

  • Configuration (Recommended "wire/logical semantics separation"):
    • dataType=Int16 (wire)
    • transformDataType=Float64 (logical)
    • quantity=1
    • transformScale=0.1
  • Driver Behavior: Read 1 word -> Parse as i16(wire) -> Apply Transform wire→logical -> Output 25.5

3.2 Coil Types (0x01/0x02)

DataTypequantityDescription
Boolean1Single bit read/write
Telemetry/AttributeNDriver will map read bit array to corresponding points. Currently recommend quantity=1 per point corresponding to one bit.

4. Batch Read/Write Planning Algorithm

The driver has a built-in Planner module responsible for aggregating scattered point requests into optimal Modbus PDUs.

  1. Grouping: Group by functionCode (0x03 and 0x04 cannot be merged).
  2. Sorting: Sort by address ascending within group.
  3. Scan & Merge:
    • Register Read (0x03/0x04): As long as (next_addr - current_end) <= maxGapRegisters and (new_end - current_start) <= maxBatchRegisters, merge into one request (Subject to protocol limit clamp).
    • Bit Read (0x01/0x02): As long as (next_addr - current_end) <= maxGapBits and (new_end - current_start) <= maxBatchBits, merge into one request.
    • Merge will produce "Hole Data", which will be read but discarded during decoding phase.

4.1 Performance Tuning Suggestions

  • High Throughput Mode:

    • Register: maxGapRegisters = 1~10, maxBatchRegisters = 100~125
    • Bit: maxGapBits = 16~200, maxBatchBits = 512~2000
    • Applicable: Concentrated point addresses, good network quality (TCP).
  • High Stability Mode:

    • Register: maxGapRegisters = 0 (No gap crossing), maxBatchRegisters = 40~80
    • Bit: maxGapBits = 0 (No gap crossing), maxBatchBits = 128~512
    • Applicable: RS-485 high interference, slow device response.