1. Protocol Introduction
Modbus is a classic industrial field communication protocol, with common forms including Modbus TCP (Ethernet) and Modbus RTU (Serial/RS-485). It uses "Register/Coil" as core abstractions:
- Coils: bit (Usually Read/Write)
- Discrete Inputs: bit (Usually Read-Only)
- Holding Registers: 16-bit register (Usually Read/Write)
- Input Registers: 16-bit register (Usually Read-Only)
NG Gateway Modbus driver adopts a Fully Asynchronous, Zero-Copy architecture, performing batch read/write of points with high throughput and low overhead on the gateway side. Supports Smart Cast (Intelligent Type Conversion) and Automatic Batch Planning.
2. Configuration Model
2.1 Channel Configuration
Channel is the boundary of "Connection and Session": The same TCP connection or the same RS-485 serial line should be modeled as a Channel.
2.1.1 connection.kind (Connection Type)
- tcp: Modbus TCP
- rtu: Modbus RTU (Serial)
2.1.2 TCP Parameters (When connection.kind = tcp)
connection.host: Remote host (IPv4 or hostname, excluding schema/port)connection.port: Port, default502
Suggestion
- Field devices mostly have fixed IPs, it is recommended to fill in IP directly; avoid extra uncertainty introduced by DNS resolution.
2.1.3 RTU Parameters (When connection.kind = rtu)
connection.port: Serial port path- Linux Example:
/dev/ttyUSB0 - Windows Example:
COM3
- Linux Example:
connection.baudRate: Baud rate (Default 9600)connection.dataBits: Data bits (5/6/7/8, Default 8)connection.stopBits: Stop bits (1/2, Default 1)connection.parity: Parity (None/Odd/Even, Default None)
2.1.4 byteOrder / wordOrder
Modbus register is a 16-bit word; when point data type is 32/64-bit, it spans multiple registers. Different devices have differences in "Byte/Word Order" implementation:
byteOrder: Order of two bytes inside a register (BigEndian/LittleEndian)wordOrder: Order of words when multiple registers are used (BigEndian/LittleEndian)
Typical Combinations:
- Common PLC:
byteOrder=BigEndian,wordOrder=BigEndian - Some devices (Especially legacy devices) use "Word Swap" for 32-bit/64-bit:
wordOrder=LittleEndian
Suggest confirming in host computer/manufacturer manual; if the read float value is "obviously absurd", prioritize checking byte/word order.
2.1.5 tcpPoolSize
tcpPoolSize is used to improve Modbus TCP throughput: The driver maintains a TCP connection pool, and selects connections in a round-robin manner within the pool during collection, thereby allowing multiple requests in flight (Still subject to core concurrency and driver internal planning constraints).
- Default Value:
1 - Recommended Range:
1..=32(Too large usually yields insignificant benefits and increases PLC/Gateway resource consumption)
WARNING
Only effective for connection.kind=tcp; RTU will force single flight (Effective value=1). When you configure tcpPoolSize > 32, the driver will clamp to 32 at runtime.
2.1.6 Batch Read Planning Parameters
| Field | Scope | Default | Description |
|---|---|---|---|
maxBatchRegisters | 0x03/0x04 (Register Read) | 120 | Max span (number of words) for a single read request. Protocol hard limit <=125, driver will clamp |
maxGapRegisters | 0x03/0x04 (Register Read) | 1 | Max "Gap" (word address difference) allowed when merging adjacent points |
maxBatchBits | 0x01/0x02 (Bit Read) | 2000 | Max span (number of bits) for a single read request. Protocol hard limit <=2000 |
maxGapBits | 0x01/0x02 (Bit Read) | 500 | Max "Gap" (bit address difference) allowed when merging adjacent points |
WARNING
maxBatch* represents "Total quantity of a range read" (span), not "Number of points".
2.2 Device Configuration
Device represents a Slave.
slaveId: Slave ID (0-255)
2.2.1 Group collection
Modbus driver enables group collection in Polling collection path, grouping key is slaveId:
- Same
slaveId: Collector will merge multiple business Devices into onecollect_data(items)call, driver will merge points and execute batch read (read request count closer to theoretical minimum), then split into respectiveNorthwardDataoutputs by businessdevice_id. - Different
slaveId: Will be split into different groups for separate collection.
2.3 Point Configuration
functionCode:ReadCoils(0x01)/ReadDiscreteInputs(0x02)ReadHoldingRegisters(0x03)/ReadInputRegisters(0x04)
address: Start address (0..65535, 0-based)quantity: Read quantity (Coil bit count or Register word count)
2.3.1 wire/logical data type & Transform (Must Read)
Modbus dataType is wire data type (Protocol/Memory layout semantics): It determines how the driver decodes from register/coil and how to write back.
If you want northward to see "Engineering Value" (e.g., register contains scaled integer), please use Point's Transform (logical semantics):
transformDataType: logical data type (logical=wire if empty)transformScale/transformOffset/transformNegate: Numeric affine transformation
Recommended Reading
For full explanation, uplink/downlink links, min/max value range, and large integer/non-numeric limits, see: Data Types and Transform Configuration.
0-based vs 1-based address problem (Must Read)
The address in the driver here is Protocol Layer 0-based Address (UI validates min 0). But many manufacturer manuals use 1-based or "Logical Address" like 4xxxx/3xxxx.
You need to convert manual address to 0-based:
- If manual says 40001 corresponds to 1st Holding Register, then protocol address is usually
0(40001-40001). - If manual directly gives "Register Offset 0/1", follow manual definition.
It is recommended to use a "Known Fixed Value" point for validation (e.g., Device Model/Firmware Version register), calibrate the address system first, then model in bulk.
How to calculate quantity
The meaning of quantity depends on functionCode:
- Coils/DiscreteInputs: Unit is bit (Coil count)
- Holding/InputRegisters: Unit is word (16-bit)
For register reads, it is recommended to calculate quantity by data_type (See 3. Data Type Mapping Table). If quantity is too small, the driver will try to perform Smart Cast (e.g., read 1 word convert to Float32); if too large, it will truncate or pad.
2.4 Action Configuration
Action is used to encapsulate a set of "Write Coil/Write Register" operations.
functionCode:WriteSingleCoil(0x05)/WriteMultipleCoils(0x0F)WriteSingleRegister(0x06)/WriteMultipleRegisters(0x10)
address: Start addressquantity: Write quantity
Automatic Function Code Inference
For northward write_point (Single Point Write) operation, if the point defines a read function code (e.g., ReadHoldingRegisters), the driver will automatically infer the write function code based on quantity:
quantity <= 1->WriteSingleRegister(0x06)quantity > 1->WriteMultipleRegisters(0x10)
3. Data Type Mapping Table (Smart Codec)
The driver has a built-in powerful codec supporting flexible conversion from register stream to strongly typed values.
3.1 Register Types (0x03/0x04)
| DataType | Recommended quantity (words) | Decoding Behavior | Smart Cast (Degrade Compatibility) |
|---|---|---|---|
| Boolean | 1 | First word != 0 is true | - |
| Int16 | 1 | Standard 16-bit signed integer | Read 4 words (i64) truncate to i16 |
| UInt16 | 1 | Standard 16-bit unsigned integer | Read 4 words (u64) truncate to u16 |
| Int32 | 2 | Standard 32-bit signed integer | If quantity=1, read i16 and promote to i32 |
| UInt32 | 2 | Standard 32-bit unsigned integer | If quantity=1, read u16 and promote to u32 |
| Float32 | 2 | IEEE754 Single Precision Float | If quantity=1, read i16 and convert to f32 |
| Float64 | 4 | IEEE754 Double Precision Float | If quantity=2, read f32 and convert to f64 |
| Int64 | 4 | Standard 64-bit signed integer | If quantity=2, read i32 and promote to i64 |
| UInt64 | 4 | Standard 64-bit unsigned integer | If quantity=2, read u32 and promote to u64 |
| Timestamp | 2 or 4 | 4 words (8 bytes): Parse as i64 millisecond timestamp 2 words (4 bytes): Parse as u32 second timestamp and auto multiply by 1000 | - |
| String | N | UTF-8 String, auto remove trailing \0 | - |
| Binary | N | Raw byte stream | - |
"Fixed Length Block + Padding" Convention for String Points (Must Read)
Modbus protocol itself does not have a "String Register" type. String reading relies entirely on Device side data storage convention. Current driver behavior for String is:
- Restore
quantityregisters into byte stream according tobyteOrder/wordOrder; - Then only remove trailing consecutive
0x00(Remove tail\0padding), then decode as UTF-8 (Invalid bytes will be shown as replacement characters).
Therefore you need to pay special attention:
quantitymust be sufficient: Unit is register (word, 2 bytes). E.g., "String length 10 bytes" usually needsquantity = 5.- Device write suggests "Full Overwrite + 0x00 Padding": Fill the entire fixed-length register block; pad remaining part with
0x00.- Ex: Fixed length 10 registers (20 bytes) storing
"a", suggest writing0x61 0x00then pad remaining 18 bytes with0x00.
- Ex: Fixed length 10 registers (20 bytes) storing
- Do not just write
a\0and leave remaining registers uncleared: If tail has old data and not0x00, driver will not truncate at first0x00, may appear as"a\0xxxx..."(Containing invisible characters/dirty tail), looking like "String incorrect".
If field device cannot guarantee clearing tail, suggest unifying "Fixed Length Block 0 Padding" protocol on device side (or host computer write side); and first verify byteOrder/wordOrder correctness with a known string register.
Details
Smart Cast Example Scenario: Device has a temperature value, actually Int16 (255 = 25.5°C), but you defined it as Float32 in platform.
- Configuration (Recommended "wire/logical semantics separation"):
dataType=Int16(wire)transformDataType=Float64(logical)quantity=1transformScale=0.1
- Driver Behavior: Read 1 word -> Parse as i16(wire) -> Apply Transform wire→logical -> Output 25.5
3.2 Coil Types (0x01/0x02)
| DataType | quantity | Description |
|---|---|---|
| Boolean | 1 | Single bit read/write |
| Telemetry/Attribute | N | Driver will map read bit array to corresponding points. Currently recommend quantity=1 per point corresponding to one bit. |
4. Batch Read/Write Planning Algorithm
The driver has a built-in Planner module responsible for aggregating scattered point requests into optimal Modbus PDUs.
- Grouping: Group by
functionCode(0x03 and 0x04 cannot be merged). - Sorting: Sort by
addressascending within group. - Scan & Merge:
- Register Read (0x03/0x04): As long as
(next_addr - current_end) <= maxGapRegistersand(new_end - current_start) <= maxBatchRegisters, merge into one request (Subject to protocol limit clamp). - Bit Read (0x01/0x02): As long as
(next_addr - current_end) <= maxGapBitsand(new_end - current_start) <= maxBatchBits, merge into one request. - Merge will produce "Hole Data", which will be read but discarded during decoding phase.
- Register Read (0x03/0x04): As long as
4.1 Performance Tuning Suggestions
High Throughput Mode:
- Register:
maxGapRegisters= 1~10,maxBatchRegisters= 100~125 - Bit:
maxGapBits= 16~200,maxBatchBits= 512~2000 - Applicable: Concentrated point addresses, good network quality (TCP).
- Register:
High Stability Mode:
- Register:
maxGapRegisters= 0 (No gap crossing),maxBatchRegisters= 40~80 - Bit:
maxGapBits= 0 (No gap crossing),maxBatchBits= 128~512 - Applicable: RS-485 high interference, slow device response.
- Register: