1. Protocol Introduction

OPC UA (OPC Unified Architecture) is a machine-to-machine communication protocol for industrial automation, maintained by the OPC Foundation. It provides a unified information model, extensible data type system, and built-in security mechanisms (Certificate, Encryption, Signing).

2. Configuration Model

2.1 Channel Configuration

Channel is the OPC UA session boundary: One Channel corresponds to one OPC UA Server (or one endpoint).

2.1.1 Application Identity

  • applicationName: Client Application Name (Required)
  • applicationUri: Client Application URI (Required)

These fields participate in UA's application description and certificate/trust chain system (especially in certificate authentication mode).

2.1.2 url (Endpoint URL)

Example

  • opc.tcp://192.168.1.10:4840
  • opc.tcp://server-hostname:4840

2.1.3 auth.kind (Authentication Mode)

  • anonymous: Anonymous (Most common)
  • userPassword: Username and Password
  • issuedToken: Issued Token (Token string)
  • certificate: Certificate mode (privateKey + certificate)

Note

Certificate content is usually stored as PEM string.

2.1.4 Security Policy & Security Mode

  • securityPolicy: e.g., None / Basic256Sha256 / Aes256Sha256RsaPss ...
  • securityMode: None / Sign / SignAndEncrypt

Best Practice

  • Production environment recommends at least Sign, preferably SignAndEncrypt.
  • If Server only opens certain policy/mode combinations, please align with Server's endpoint configuration.

2.1.5 Collection Mode: readMode

  • Subscribe: Driver creates Subscription + MonitoredItems, Server pushes changes (Recommended).
  • Read: Active Read by collection period (Suitable for few points or Server does not support subscription/limits subscription).

Note

Subscribe mode is more "Event Driven", more efficient for high-frequency changing points, but pay attention to subscription batch and keep-alive parameters.

2.1.6 Session & Keep-Alive Parameters

  • sessionTimeout: Session timeout (ms, default 30000)
  • keepAliveInterval: Keep-alive interval (ms, default 30000)
  • maxFailedKeepAliveCount: Max failed keep-alive count (Default 3)
  • subscribeBatchSize: Subscription batch size (Default 256)

Tuning Suggestion

  • When there are many points, appropriately increasing subscribeBatchSize can reduce create/modify request times, but too large may trigger server-side limits.
  • keepAliveInterval should not be too small (increases Server pressure), nor too large (slow fault detection); default value is usually a reasonable starting point.

2.2 Device Configuration

OPC UA driver's device driver configuration is empty.

Modeling Suggestion

  • You can model "A production line/A section/A subsystem" as a Device for organizing points and northward topic routing.

Grouped collection

When OPC UA uses Read (Periodic Collection) mode, and there are multiple business Devices under the same Channel, OPC UA driver will enable grouped collection: Collector will merge points of these Devices into one collect_data(items) call, driver will merge NodeIds for one batch Read, then split into respective NorthwardData outputs by device_id.

2.3 Point Configuration

  • nodeId: OPC UA NodeId string

2.4 Action Configuration

Action is used to encapsulate a set of "Write Node" operations; Action itself does not carry protocol detail configuration.

  • Key Semantics: OPC UA write target NodeId should be configured on Action's inputs(Parameter), i.e., each parameter specifies the NodeId to write via Parameter.driver_config.nodeId.

Parameter-level driver configuration fields (Each input parameter):

  • nodeId: OPC UA NodeId string

TIP

For NodeId format and selection method, see NodeId Syntax.

3. Data Type Mapping Table

UA Variant (Scalar)Recommended DataTypeDescription
BooleanBoolean-
SByte/ByteInt8/UInt8-
Int16/UInt16Int16/UInt16-
Int32/UInt32Int32/UInt32-
Int64/UInt64Int64/UInt64-
Float/DoubleFloat32/Float64-
StringStringCan also map to Timestamp (RFC3339) or Binary (hex string)
ByteStringBinary-
DateTimeTimestampTimestamp semantics is i64 milliseconds

3.1 Read Path

  • Numeric Variant (SByte/Int16/Int32/Int64/Float/Double etc.):
    • First decode by wire data type, then convert wire→logical by logical data type + Transform.
  • Variant::Boolean: Same as above (Recommend logical as Boolean, avoid non-numeric mapping restrictions).
  • Variant::String:
    • DataType::String: Output string directly.
    • DataType::Timestamp: Try parsing RFC3339.
    • DataType::Binary: Try parsing hex string.
  • Variant::ByteString: Recommend mapping to Binary.
  • Variant::DateTime: Recommend mapping to Timestamp or String.
  • Variant::Array: Not supported in current version, returns empty (Point will not produce value).

Important

If you need array/structure, suggest providing scalar nodes on Server side, or extending "Structure/Array" to JSON mapping capability on edge side.

3.2 Write Path

When writing, force convert according to Point's data_type and generate Variant; Timestamp will be converted to UA DateTime (Write fails if timestamp is invalid).

Best Practice

  • Try to keep Point/Parameter data_type consistent with Server node's real type, avoiding precision/range issues caused by implicit conversion.
  • If Server node is array/structure: Suggest providing scalar nodes on Server side, or extending "Structure/Array → JSON" capability on edge side; current version does not output array values.

Released under the Apache License 2.0.